DESCRIPTION
The Powers 430 Hi/Lo Supply Fixture is a pre-piped system
consisting of two thermostatic valves and a PRV, designed
to provide consistent temperature control over a wide range
of flow requirements.
The unit includes: A Powers Series 430 thermostatic mixing
valve, a Powers Series 420 or 427 thermostatic mixing valve,
a Pressure Reducing Valve (PRV), pressure gauges, union
inlet strainer checkstops, dial thermometer, shut-off ball
valve, and interconnecting piping.
All components are pre-assembled for easy installation. The
stainless steel or durable white baked enamel steel cabinets
are designed for recessed or wall mount installation and pro-
vide protected access to the system.
OPERATION
This two valve supply fixture has a low capacity valve
that works in parallel with a high capacity valve.
During low demand, the low capacity valve will han-
dle the load requirements. As the load demand is
increased, the pressure reducing valve, which is set
at a certain pressure differential, will open and allow
flow through the high capacity valve to assist the low
capacity valve in meeting the load requirements.
APPLICATION
This is a typical application of the Hi/Lo Supply
Fixture for recirculation. Basic guidelines for
recirculating are provided below. Following
these guidelines will ensure stable
control of the domestic water
system during normal and
low/no use periods. Improper
piping causes the recirculat-
ing system to have erratic
pressure and temperature
fluctuations.
For Capacity requirements,
Refer to Form #MV430-3.5 or
the Hi/Lo Supply Fixture Brochure.
DO NOT recirculate low temperature hot water (LTHW)
and high temperature hot water (HTHW) with one pump;
return water may come back hotter than mixer set point.
To minimize natural heat convection, locate master
mixer below hot water source, or install mixer with heat
trap (a two-foot drop in the pipe line) as shown.
Do use two (2) circulating pumps. Use check valves to
prevent reverse flow.
Always use an Aquastat set at a temperature below set
point of mixer.
Be certain HTHW cannot be introduced into cold side of
mixer.
Always tie LTHW return to cold water side of mixing
valve, as well as back to hot water source.
WARNING
DO NOT OMIT THE LTHW CONNECTIONS; scalding and
severe personal injury may result from return supply
temperatures approaching hot water heater tempera-
tures.
WATER
HEATER
STEAM
INPUT
PRV
HTHW
HTHW RETURN
CW
HEAT TRAP
LTHW
RETURN
LTHW
AQUASTAT
PUMP
Hi
AQUASTAT
PUMP
Supply Pressure
Gauge
Outlet Pressure
Gauge
B a ll V alv e
B a ll V alv e
Checkstops
Checkstops
Lo
EXPANSION
TANK
Sensor
Shock Absorber
S ole n oid V a lve
(O p tio n a l)
2
qua
entry
A
S
uality…Our CommitmentQ
qua
entry
A
S
SERIES 460 ALARM
°F
TEST
Set
Reset
TECHNICAL INSTRUCTIONS
HI/LO SUPPLY FIXTURE SYSTEM
Operation, Testing, Maintenance
TI430-420
Vue de la page 0
1 2 3 4

Résumé du contenu

Page 1 - HI/LO SUPPLY FIXTURE SYSTEM

DESCRIPTIONThe Powers 430 Hi/Lo Supply Fixture is a pre-piped systemconsisting of two thermostatic valves and a PRV, designedto provide consistent tem

Page 2 - INDIVIDUAL SETTING PROCEDURES

PRIOR TO INSTALLATION1. Flush all piping thoroughly.2. Make sure all valve handles are rotated fully clockwise(off).3. If you use copper tubing, exces

Page 3 - TROUBLESHOOTING

420 Valve5. Use the handle to close the valve (rotate fully clockwise).Replace lock washer and handle retaining screw.Adjust the temperature of the 43

Page 4 - PREVENTIVE MAINTENANCE

Outlet temperature too low on low and high flow…• The hot water supply temperature is too low. You musthave a supply temperature of at least 25°F high