Vue de la page 0
Description n
Capacity n
Two Valve PowerStation
Supply Fixture
Capacity up to 271 gpm @ 45psi
Technical Instructions
IS-P-SF-2VPS
Advanced Thermal Activation
Maximum Operating Pressure ............................. 125psi (861 kPa)
Maximum Hot Water Temperature ...................... 200°F (93°C)
Minimum Hot Water Supply Temp.* ................... 5°F (3°C) Above Set Point
Hot Water Inlet Temperature Range ................... 120 -180°F (49 - 82°C)
Cold Water Inlet Temperature Range ................. 40 - 80°F (4 - 27°C)
Minimum Flow** ...................................................... 0.5 gpm (1.89 lpm)
Temp. Adjustment Range *** ............................... 90 - 160°F (32 - 71°C)
Listing/Compliance (Valve Only)............................ ASSE 1017, CSA B125
* With Equal Pressure
** Minimum flow when 2VPS is installed at or near hot water source recirculating tempered
water with a properly sized continuously operating recirculating pump.
*** Note: Low limit cannot be less than the cold water temperature. For best operation, hot
water should be at least 5°F (3°C) above desired set point.
Specifications n
Flow Capacity at 50-50 Mixed Ratio
Pressure Drop Across Valve
Model
Min. Flow
CV
5psi 10psi 20psi 30psi 45psi 60psi
to ASSE 1017
(34 kPa) (69 kPa) (138 kPa) (207 kPa) (310 kPa) (414 kPa)
MM431HL and
LFMM431HL
0.5 gpm
9.70
22 gpm 31 gpm 43 gpm 53 gpm 65 gpm 75 gpm
1.89 lpm 83 lpm 117 lpm 163 lpm 201 lpm 246 lpm 284 lpm
MM432HL and
LFMM432HL
0.5 gpm
13.00
29 gpm 41 gpm 58 gpm 66 gpm 87 gpm 93 gpm
1.89 lpm 110 lpm 155 lpm 220 lpm 250 lpm 329 lpm 352 lpm
MM433HL and
LFMM433HL
0.5 gpm
19.80
44 gpm 63 gpm 86 gpm 108 gpm 133 gpm 153 gpm
1.89 lpm 167 lpm 238 lpm 326 lpm 409 lpm 503 lpm 579 lpm
MM434HL and
LFMM434HL
0.5 gpm
24.90
56 gpm 79 gpm 111 gpm 136 gpm 167 gpm 193 gpm
1.89 lpm 212 lpm 299 lpm 420 lpm 515 lpm 632 lpm 731 lpm
MM435HL and
LFMM435HL
3.0 gpm
27.70
62 gpm 88 gpm 124 gpm 152 gpm 186 gpm 215 gpm
11.0 lpm 235 lpm 333 lpm 469 lpm 575 lpm 704 lpm 814 lpm
SH1432DV and
LFSH1432DV
2 gpm
27.40
61 gpm 87 gpm 123 gpm 150 gpm 184 gpm 213 gpm
8 lpm 231 lpm 329 lpm 466 lpm 568 lpm 697 lpm 806 lpm
SH1434DV and
LFSH1434DV
2 gpm
37.40
84 gpm 118 gpm 167 gpm 205 gpm 251 gpm 290 gpm
8 lpm 318 lpm 447 lpm 632 lpm 776 lpm 950 lpm 1098 lpm
SH1432HL and
LFSH1432HL
1 gpm
30.00
67 gpm 95 gpm 134 gpm 164 gpm 201 gpm 232 gpm
4 lpm 254 lpm 360 lpm 507 lpm 621 lpm 761 lpm 878 lpm
SH1434HL and
LFSH1434HL
1 gpm
40.40
90 gpm 128 gpm 181 gpm 221 gpm 271 gpm 313 gpm
4 lpm 341 lpm 485 lpm 685 lpm 837 lpm 1026 lpm 1185 lpm
WARNING: TO ENSURE THE
ACCURATE AND RELIABLE
OPERATION OF THIS PRODUCT, IT IS
ESSENTIAL TO:
Properly size each valve based on the indi-
vidual application.
Properly design the recirculation system to
minimize pressure and temperature variations.
Conduct an annual maintenance program to
ensure proper operation of all critical com-
ponents.
THIS VALVE MUST BE USED IN
CONJUNCTION WITH TEMPERATURE
ACTUATED POINT-OF-USE DEVICES THAT
COMPLY WITH ASSE 1016, 1069, OR 1070.
FAILURE TO COMPLY WITH PROPER
INSTALLATION INSTRUCTIONS COULD
CONTRIBUTE TO VALVE FAILURE, RESULTING
IN IN JURY OR DEATH.
!
Powerstation
is a complete, fully assembled water tempering system, designed to
provide safe water throughout commercial and institutional facilities. Powerstation
features the HydroGuard
®
LM490 or LFLM490, HydroGuard
®
XP MM430 or LFMM430,
and SH1430 or LFSH1430 Master Tempering Series valve which utilize parafn-based
actuation technology to sense and to adjust outlet temperature. Each Powerstation
is mounted on heavy-duty, welded struts and factory tested as a complete system.
Each Powerstation
includes an engineer specied circulator, GFCI outlet, combination
temperature/pressure gauges and Powers' triple-duty checkstops. Optional equipment
includes an Aquastat and/or Powers' exclusive automatic balancing valve and a internal
bypass loop for and easy set-up.
Vue de la page 0
1 2 3 4

Résumé du contenu

Page 1 - Technical Instructions

Description nCapacity nTwo Valve PowerStation™ Supply Fixture Capacity up to 271 gpm @ 45psiTechnical InstructionsIS-P-SF-2VPSAdvanced Thermal Activat

Page 2

NOTE: Perform all 22 steps before moving on to the next sec-tion. Steps 1 thru 22 explain how to set the thermostatic valve.1. Close B3, B4 and B6.2

Page 3 - Legends n

Item Number Item Description Options Quantity Required1 Ball Valve Std 52 Temperature / Pressure Gauge Std 43 Triple Duty Checkstop Std 44 Pressure Ga

Page 4 - Warranty n

USA:  Phone: 1.800.669.5430 • Fax 1.847. 229 . 0526 • www.powerscontrols.comCanada:  Phone: 1.888.208.8927 • Fax 1.888. 479.2887 • www.powerscontrols.