Powers PowerStation XP Single and Multi-Valve Series - Si Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Accessoires pour l'eau Powers PowerStation XP Single and Multi-Valve Series - Si. Powers PowerStation XP Single and Multi-Valve Series - Single Valve 1 - 208 gpm User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 4
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
Description n
Capacity n
Single Valve PowerStation
Supply Fixture
Capacity up to 208 gpm@45psi
Technical Instructions
IS-P-SF-SVPS
PowerStation
is a complete, fully assembled water tempering system, designed
to provide safe water throughout commercial and institutional facilities.
PowerStation
features the HydroGuard
®
XP MM430, LFMM430 or SH1430,
LFSH1430 master tempering series valve which utilize paraffin-based actuation
technology to sense and adjust outlet temperature. Each PowerStation
is
mounted heavy-duty, welded struts and factory tested as a complete system.
Each PowerStation
includes an engineer specified circulator, GFCI outlet,
combination temperature/pressure gauges and Powers' triple-duty checkstops.
Optional equipment includes an Aquastat and/or Powers' exclusive automatic
balancing valve and an internal bypass loop for easy set-up.
Maximum Operating Pressure ............................. 125psi (861 kPa)
Maximum Hot Water Temperature ...................... 200°F (93°C)
Minimum Hot Water Supply Temp*. ..................... 5°F (3°C) Above Set-Point
Hot Water Inlet Temperature Range ................... 120 -180°F (49 - 82°C)
Cold Water Inlet Temperature Range ................. 40 - 80°F (4 - 27°C)
Minimum Flow** ...................................................... 0.5 gpm (1.89 lpm)
Temp. Adjustment Range *** ............................... 90 - 160°F (32 - 71°C)
Listing/Compliance (Valve Only)............................ ASSE 1017, CSA B125
* With Equal Pressure
** Minimum flow when PowerStation™ is installed at or near hot water source recirculating
tempered water with a properly sized continuously operating recirculating pump.
*** Note: Low limit cannot be less than the cold water temperature. For best operation,
hot water should be at least 5°F (3°C) above desired set point.
Specifications n
Flow Capacity at 50-50 Mixed Ratio
Pressure Drop Across Valve
Model
Min. Flow
C
V
5psi 10psi 20psi 30psi 45psi 60psi
to ASSE 1017
(34 kPa) (69 kPa) (138 kPa) (207 kPa) (310 kPa) (414 kPa)
MM431 and
LFMM431
3 gpm
6.32
14 gpm 20 gpm 28 gpm 35 gpm 42 gpm 49 gpm
11 lpm 53 lpm 76 lpm 106 lpm 132 lpm 159 lpm 185 lpm
MM432 and
LFMM432
4 gpm
9.49
21 gpm 30 gpm 42 gpm 52 gpm 64 gpm 74 gpm
15 lpm 80 lpm 114 lpm 159 lpm 197 lpm 242 lpm 280 lpm
MM433 and
LFMM433
5 gpm
16.44
37 gpm 52 gpm 74 gpm 90 gpm 110 gpm 127 gpm
19 lpm 140 lpm 197 lpm 280 lpm 341 lpm 416 lpm 481 lpm
MM434 and
LFMM434
7 gpm
21.50
48 gpm 68 gpm 96 gpm 118 gpm 144 gpm 167 gpm
26 lpm 182 lpm 257 lpm 363 lpm 447 lpm 545 lpm 632 lpm
MM435 and
LFMM435
10 gpm
31.00
69 gpm 98 gpm 139 gpm 170 gpm 208 gpm 240 gpm
38 lpm 261 lpm 371 lpm 526 lpm 644 lpm 787 lpm 908 lpm
SH1432 and
LFSH1432
1 gpm
8.54
19 gpm 27 gpm 38 gpm 47 gpm 57 gpm 66 gpm
4 lpm 72 lpm 102 lpm 144 lpm 178 lpm 216 lpm 250 lpm
SH1434 and
LFSH1434
1 gpm
19.00
42 gpm 60 gpm 85 gpm 104 gpm 127 gpm 147 gpm
4 lpm 159 lpm 227 lpm 322 lpm 394 lpm 481 lpm 556 lpm
SH1435 and
LFSH1435
5 gpm
30.00
67 gpm 95 gpm 134 gpm 164 gpm 201 gpm 232 gpm
19 lpm 254 lpm 360 lpm 507 lpm 621 lpm 761 lpm 878 lpm
Advanced Thermal Activation
WARNING: TO ENSURE THE
ACCURATE AND RELIABLE
OPERATION OF THIS PRODUCT, IT IS
ESSENTIAL TO:
Properly size each valve based on the indi-
vidual application.
Properly design the recirculation system to
minimize pressure and temperature variations.
Conduct an annual maintenance program to
ensure proper operation of all critical com-
ponents.
THIS VALVE MUST BE USED IN
CONJUNCTION WITH TEMPERATURE
ACTUATED POINT-OF-USE DEVICES THAT
COMPLY WITH ASSE 1016, 1069, OR 1070.
FAILURE TO COMPLY WITH PROPER
INSTALLATION INSTRUCTIONS COULD
CONTRIBUTE TO VALVE FAILURE, RESULTING
IN IN JURY OR DEATH.
!
Vue de la page 0
1 2 3 4

Résumé du contenu

Page 1 - Technical Instructions

Description nCapacity nSingle Valve PowerStation™ Supply FixtureCapacity up to 208 gpm@45psiTechnical InstructionsIS-P-SF-SVPSPowerStation™ is a compl

Page 2

NOTE: Perform all 15 steps before moving on to the next sec-tion. Steps 1-15 are to set thermostatic valve. 1. Close B3, B4 and B6.2. Close D1 and

Page 3 - Legends n

Item Number Item Description Options Quantity Required1 Ball Valve Std 42 Temperature / Pressure Gauge Std 43 Triple Duty Check Stop Std 24 Thermostat

Page 4 - Warranty n

USA:  Phone: 1.800.669.5430 • Fax 1.847. 229 . 0526 • www.powerscontrols.comCanada:  Phone: 1.888.208.8927 • Fax 1.888.479.2887 • www.powerscontrols.c