Description n
Table 1 Capacity n
HydroGuard
®
XP SH1434 & LFSH1434 Triple,
Quad & Six Valve Hi/Lo Supply Fixture
Technical Instructions
IS-P-SF-SH1434-TV_QV_6V
Advanced Thermal Activation
Powers' HydroGuard
®
XP Series SH1434 & LFSH1434 Triple, Quad and Six Valve
Hi/Lo's are fully assembled, factory tested systems, designed to provide safe
water throughout commercial and institutional facilities. Each consists of MM434
or LFMM434 and SH1434 or LFSH1434 Master Tempering Valves which utilize par-
affin-based actuation technology to sense and adjust outlet temperature. Each
system includes a PRV, ball valves, pressure/temperature gauges and Powers'
triple-duty check stops and are supported by heavy-duty welded struts. Optional
equipment includes cabinets and/or Powers' AquaSentry
®
2 high-temperature
alarm system. (Not available with LFSH1434 Series).
Maximum Operating Pressure ............................. 125psi (861 kPa)
Maximum Hot Water Temperature ...................... 200°F (93°C)
Minimum Hot Water Supply Temp* .................... 5°F (3°C) Above Set Point
Hot Water Inlet Temperature Range ................... 120 -180°F (49 - 82°C)
Cold Water Inlet Temperature Range ................. 40 - 80°F (4 - 27°C)
Minimum Flow** ...................................................... 0.5 gpm (1.89 lpm)
Temp. Adjustment Range *** ............................... 90 - 160°F (32 - 71°C)
Listing/Compliance (Valve Only)............................ ASSE 1017, CSA B125
*With Equal Pressure
**Minimum flow when Hi/Lo valve is installed at or near hot water source recirculating tempered
water with a properly sized continuously operating recirculating pump.
***Note: Low limit cannot be less than the cold water temperature. For best operation, hot
water should be at least 5°F (3°C) above desired set point.
Specifications n
Operation n
The Triple, Quad and Six Valves Hi/Lo feature one low capacity valve that works in
parallel with multiple high capacity valves. During low demand, the low capacity
valve handles the load requirements. As the load demand increases, the pres-
sure reducing valve, which is set at a certain pressure differential, will open and
allow flow through the high capacity valves to assist the low capacity valve in
meeting the increased load requirements.
Flow Capacity at 50-50 Mixed Ratio
Pressure Drop Across Valve
Model
Min. Flow
C
V
5psi 10psi 20psi 30psi 45psi 60psi
to ASSE 1017
(34 kPa) (69 kPa) (138 kPa) (207 kPa) (310 kPa) (414 kPa)
SH1434TV and
LFSH1434TV
1 gpm
62.0
139 gpm 196 gpm 277 gpm 340 gpm 416 gpm 480 gpm
4 lpm 526 lpm 742 lpm 1049 lpm 1287 lpm 1575 lpm 1817 lpm
SH1434QV and
LFSH1434QV
1 gpm
83.3
186 gpm 263 gpm 373 gpm 456 gpm 559 gpm 645 gpm
4 lpm 704 lpm 996 lpm 1412 lpm 1726 lpm 2116 lpm 2442 lpm
SH1434-6V and
LFSH1434-6V
1 gpm
126.3
282 gpm 400 gpm 565 gpm 692 gpm 847 gpm 978 gpm
4 lpm 1067 lpm 1514 lpm 2139 lpm 2620 lpm 3206 lpm 3702 lpm
WARNING: TO ENSURE THE
ACCURATE AND RELIABLE
OPERATION OF THIS PRODUCT, IT IS
ESSENTIAL TO:
Properly size each valve based on the indi-
vidual application.
Properly design the recirculation system to
minimize pressure and temperature variations.
Conduct an annual maintenance program to
ensure proper operation of all critical com-
ponents.
THIS VALVE MUST BE USED IN
CONJUNCTION WITH TEMPERATURE
ACTUATED POINT-OF-USE DEVICES THAT
COMPLY WITH ASSE 1016, 1069, OR 1070.
FAILURE TO COMPLY WITH PROPER
INSTALLATION INSTRUCTIONS COULD
CONTRIBUTE TO VALVE FAILURE, RESULTING
IN IN JURY OR DEATH.
!
Vue de la page 0
1 2 3 4

Résumé du contenu

Page 1 - Technical Instructions

Description nTable 1 Capacity nHydroGuard® XP SH1434 & LFSH1434 Triple, Quad & Six Valve Hi/Lo Supply FixtureTechnical InstructionsIS-P-SF-SH1

Page 2 - SH1434QV or LFSH1434QV

1. Flush all piping thoroughly before installing.2. Make sure all ball valve handles are in "OFF" position.3. In order to make any tempe

Page 3 - SH1434-6V

3SH1434QV Continued1. Close the ball valve at the outlet of the SH1434 or LFSH1434 and MM434 or LFMM434 valve #2, #3, #4 and #5.2. Open the ball v

Page 4 - Warranty n

USA:  Phone: 1.800.669.5430 • Fax 1.847. 229. 0526 • www.powerscontrols.comCanada:  Phone: 1.888.208.8927 • Fax 1.888. 479.2887 • www.powerscontrols.c